Most building codes now require performance testing of HVAC ductwork and building envelope air tightness. We offer testing and consultation to ensure you meet the requirements such as the 2009 or later International Energy Conservation Code IECC. See our blower door, duct leakage & energy code testing page.
By being able to test total leakage or leakage to outdoors, we significantly increase your odds of passing for code.
Duct Leakage Testing

A duct leakage test shows how much of the air your heating and cooling system moves is escaping through gaps and loose connections in the ductwork. The registers are sealed off, a calibrated duct testing fan is connected to the system, and the leakage is measured at a standard test pressure.
For builders, the energy code often requires a duct leakage test along with a blower door air leakage test. For homeowners, duct testing can be part of a home energy audit, so leaky ducts can be found and sealed.
Before the test we confirm that the heating and cooling system can be shut off and that we can reach the registers and the air handler. Each supply and return register is taped or temporarily sealed, a calibrated duct testing fan is connected to the system, usually at the air handler or a large return, and the ducts are brought to a standard test pressure. The airflow the fan needs to hold that pressure is the duct leakage, measured in cubic feet per minute (CFM).
On new construction the test can be done at rough-in, before the drywall goes up, or after construction is finished. Testing at rough-in makes leaks much easier to reach and seal.
A total leakage test measures every leak in the duct system, including leaks into the living space. A leakage-to-outside test is run with a blower door at the same time, so only the air lost to attics, crawlspaces, garages and the outdoors is counted. Which test applies depends on the code your project falls under, so we confirm the method with you before testing.
Builders and HVAC contractors need a duct leakage test on new homes and additions with forced-air ductwork when the local energy code calls for one. Homeowners can benefit too, especially with rooms that are hard to heat or cool, or ducts that run through an attic, crawlspace or garage.
Results are reported as CFM of leakage at the test pressure. For code work they are compared with the conditioned floor area the system serves, and you get a written report of the results that you can give your code official. For homeowners, duct results are part of the energy audit report, along with recommendations for sealing.
See blower door, duct leakage and energy code testing, and our energy code testing for contractors. We serve Southern Maine and Seacoast New Hampshire, including Berwick, South Berwick, Eliot, Kittery, York, Wells and Sanford in ME, and Portsmouth, Dover and Rochester in NH. Call (603) 828-2290 or contact us to schedule a test.